Boiler Maintenace Checklist |
|
• Check Boiler pressure with an accurate gauge. • Check expansion tank “tap test” or sight glass for signs of water logging. • Check PRV (pop off) position and piping, outlet clear, valve vertical, pointed down. • Take gas pressure reading and adjust to name plate and/or follow high altitude • Check for soot in the heat exchanger, even trace amounts can indicate a big problem. • Check draft of atmospheric burner, BIC test on the draft hood. • Take temperature rise of boiler/system. • Boiler type: Copper, cast, steel, etc. • Pump size, piping size; size consistent? • Note system static (pump and boiler off) pressure. • System contains Glycol? At what level? • If flow is in question take pressure readings on either side of pump as close to the pump as possible. • Ideally all system pumps should pump away from the expansion tank. • Auto fill present? Open or closed? If opening a closed fill valve, note system pressure and turn • Commercial boilers need to have a manual reset high limit control per code. • Does the system have a backflow prevention device? |
|